  • Series resonance

    110kV (manual split type) current and voltage transformer resonance

    Views:

    ●Product introduction

    Product name: 110kV (manual split type) current and voltage transformer resonance
    Product specifications: XSN (XZ)-40kVA/80kV
    Applicable test product: Transformer
    Test product range: 110kV class transformer, CVT

    Product role and function: 1. Help customers to achieve preventive AC withstand voltage test and handover AC withstand voltage test of various tested products;
    2. Test cross-linked rubber-plastic power cables, power transformers, GIS, transformers, insulators, generators, switches and other test products insulation withstand various overvoltage capabilities and AC withstand voltage test for capacitive loads.

    Product nicknames: series resonance withstand voltage test equipment, AC withstand voltage test equipment, inspection resonant booster device, series resonance withstand voltage tester.

    Test object: 110kV class transformer, CVT, capacitance 0.01-0.02uF, test frequency is 50Hz, test voltage does not exceed 80kV.

    ●Technical parameters

    1. Product core parameters:
    Rated capacity: 40kVA;
    Input power: 220V, frequency is 50Hz;
    Rated voltage: 80kV;
    Rated current: 0.5A;
    Working frequency: 50Hz;
    Waveform distortion rate: output voltage waveform distortion rate ≤ 1%;
    Working time: allow continuous 5min under rated load; overvoltage 1.1 times 1 minute;
    Temperature rise: the temperature rise ≤65K after continuous operation for 5 minutes under rated load;
    Quality factor: the device itself Q≥10 (f=50Hz);
    Measurement accuracy: system effective value 1.5;

    2. Excitation transformer JLB-3kVA/5kV 1 unit
    Rated capacity: 3kVA;
    Input voltage: 0-200V, single phase;
    Output voltage: 5kV;
    Structure: dry type;
    Weight: about 38 kg;

    3. Control box parameters
    Rated output capacity: 3kVA
    Working power supply: 220±10%V power frequency
    Output voltage: 0-250V,
    Rated input current: 12A
    Rated output current: 12A
    Running time: continuous 5min under rated capacity
    The maximum temperature of the components during continuous operation for 5 min under the rated capacity is ≤65K;
    Noise level: ≤50dB
    Weight: about 15kg;

    4. Adjustable reactor DK-20kVA/40kV 2 sections
    Rated capacity: 205kVA;
    Rated voltage: 40kV;
    Rated current: 0.5A;
    Inductance: 250H-510H/single section adjustable
    Quality factor: Q≥10 (f=50Hz);
    Weight: about 45kg;